30 CFR 77.801 - Grounding resistors.

Code of Federal Regulations - Title 30: Mineral Resources

Linked as:

Text


TITLE 30 - MINERAL RESOURCES

CHAPTER I - MINE SAFETY AND HEALTH ADMINISTRATION, DEPARTMENT OF LABOR

SUBCHAPTER O - COAL MINE SAFETY AND HEALTH

PART 77 - MANDATORY SAFETY STANDARDS, SURFACE COAL MINES AND SURFACE WORK AREAS OF UNDERGROUND COAL MINES

subpart i - SURFACE HIGH - VOLTAGE DISTRIBUTION

77.801 - Grounding resistors.

The grounding resistor, where required, shall be of the proper ohmic value to limit the voltage drop in the grounding circuit external to the resistor to not more than 100 volts under fault conditions. The grounding resistor shall be rated for maximum fault current continuously and insulated from ground for a voltage equal to the phase-to-phase voltage of the system.