10 CFR 434.515 - Receptacles.

Code of Federal Regulations - Title 10: Energy

Linked as:

Text


Title 10: Energy

CHAPTER II: DEPARTMENT OF ENERGY

SUBCHAPTER D: ENERGY CONSERVATION

PART 434: ENERGY CODE FOR NEW FEDERAL COMMERCIAL AND MULTI-FAMILY HIGH RISE RESIDENTIAL BUILDINGS

Subpart E: Building Energy Cost Compliance Alternative

434.515 - Receptacles.

515.1Receptacle loads and profiles are default assumptions. The same assumptions shall be made in calculating Design Energy Consumption as were used in calculating the Energy Cost Budget.

515.2Receptacle loads include all general service loads that are typical in a building. These loads exclude any process electrical usage and HVAC primary or auxiliary electrical usage. Table 515.2, Receptacle Power Densities, establishes the density, in W/ft2, to be used for each building type. The receptacle energy profiles shall be the same as the lighting energy profiles in Table 513.2.b. This profile establishes the percentage of the receptacle load that is switched on by hour of the day and by building type.

Table 515.2?Receptacle Power DensitiesIncluded in Lights and Equipment portions of Tables 512.2 a and b.
Building typeW/ft2 ofconditioned floor

area

Assembly0.25
Office0.75
Retail0.25
Warehouse0.1
School0.5
Hotel/Motel0.25
Restaurant0.1
Health1.0
Multi-family High Rise Residential