46 CFR 39.20-13 - High and low vapor pressure protection for tankshipsT/ALL.

Code of Federal Regulations - Title 46: Shipping

Linked as:

Text


TITLE 46 - SHIPPING

CHAPTER I - COAST GUARD, DEPARTMENT OF HOMELAND SECURITY

SUBCHAPTER D - TANK VESSELS

PART 39 - VAPOR CONTROL SYSTEMS

39.20 - 13 - High and low vapor pressure protection for tankshipsT/ALL.

Each tankship vapor collection system must be fitted with a pressure sensing device that senses the pressure in the main vapor collection line, which: (a) Has a pressure indicator located on the vessel where the cargo transfer is controlled; and (b) Has a high pressure and a low pressure alarm that: (1) Is audible and visible on the vessel where cargo transfer is controlled; (2) Alarms at a high pressure of not more than 90 percent of the lowest pressure relief valve setting in the cargo tank venting system; and (3) Alarms at a low pressure of not less than four inches water gauge (0.144 psig) for an inerted tankship, or the lowest vacuum relief valve setting in the cargo tank venting system for a non-inerted tankship.