49 CFR 236.552 - Insulation resistance; requirement.

Code of Federal Regulations - Title 49: Transportation

Linked as:

Text




 

Title 49: Transportation

Subtitle B: Other Regulations Relating to Transportation (Continued)

CHAPTER II: FEDERAL RAILROAD ADMINISTRATION, DEPARTMENT OF TRANSPORTATION

PART 236: RULES, STANDARDS, AND INSTRUCTIONS GOVERNING THE INSTALLATION, INSPECTION, MAINTENANCE, AND REPAIR OF SIGNAL AND TRAIN CONTROL SYSTEMS, DEVICES, AND APPLIANCES

Subpart E: Automatic Train Stop, Train Control and Cab Signal Systems

: Rules and Instructions; Locomotives

236.552 - Insulation resistance; requirement.

When periodic test prescribed in ? 236.588 is performed, insulation resistance between wiring and ground of continuous inductive automatic cab signal system, automatic train control system, or automatic train stop system shall be not less than one megohm, and that of an intermittent inductive automatic train stop system, not less than 250,000 ohms. Insulation resistance values between periodic tests shall be not less than 250,000 ohms for a continuous inductive automatic cab signal system, automatic train control system, or automatic train stop system, and 20,000 ohms for an intermittent inductive automatic train stop system.

[49 FR 3387, Jan. 26, 1984]