46 CFR 181.310 - Fire main and hydrants.

Code of Federal Regulations - Title 46: Shipping

Linked as:

Text




 

Title 46: Shipping

CHAPTER I: COAST GUARD, DEPARTMENT OF HOMELAND SECURITY (CONTINUED)

SUBCHAPTER T: SMALL PASSENGER VESSELS (UNDER 100 GROSS TONS)

PART 181: FIRE PROTECTION EQUIPMENT

Subpart C: Fire Main System

181.310 - Fire main and hydrants.

(a) A vessel that has a power driven fire pump must have a sufficient number of fire hydrants to reach any part of the vessel using a single length of fire hose.

(b) Piping, valves, and fittings in a fire main system must comply with subpart G, part 182, of this chapter.

(c) Each fire hydrant must have a valve installed to allow the fire hose to be removed while the fire main is under pressure.

[CGD 85-080, 61 FR 982, Jan. 10, 1996, as amended at 62 FR 51358, Sept. 30, 1997]