46 CFR 111.97-9 - Overcurrent protection.

Code of Federal Regulations - Title 46: Shipping

Linked as:

Text


TITLE 46 - SHIPPING

CHAPTER I - COAST GUARD, DEPARTMENT OF HOMELAND SECURITY

SUBCHAPTER J - ELECTRICAL ENGINEERING

PART 111 - ELECTRIC SYSTEMS - GENERAL REQUIREMENTS

111.97 - 9 - Overcurrent protection.

Overcurrent devices must be arranged to isolate a fault with as little disruption of the system as possible. The relationship between the load and the rating or setting of overcurrent devices must meet the following: (a) The rating or setting of each feeder overcurrent device must be not less than 200 percent of its maximum load.

  (b) The rating or setting of a branch circuit overcurrent device must be not more than 25 percent of that of the feeder overcurrent device.