46 CFR 52.01-110 - Water-level indicators, water columns, gauge-glass connections, gauge cocks, and pressure gauges (modifies PG60).
Code of Federal Regulations - Title 46: Shipping (2005)
Linked as:Code of Federal Regulations - Title 46: Shipping (2005)
Linked as:
Text
TITLE 46 - SHIPPING
CHAPTER I - COAST GUARD, DEPARTMENT OF HOMELAND SECURITY
SUBCHAPTER F - MARINE ENGINEERING
PART 52 - POWER BOILERS
52.01 - 110 - Water - level indicators, water columns, gauge - glass connections, gauge cocks, and pressure gauges (modifies PG60).
(a) Boiler water level devices. Boiler water level devices shall be as indicated in PG60 of the ASME Code except as noted otherwise in this section.
(b) Water level indicators. (Modifies PG60.1.) (1) Each boiler, except those of the forced circulation type with no fixed water line and steam line, shall have two independent means of indicating the water level in the boiler connected directly to the head or shell. One shall be a gage lighted by the emergency electrical system (See Subpart 112.15 of Subchapter J (Electrical Engineering) of this chapter) which will insure illumination of the gages under all normal and emergency conditions. The secondary indicator may consist of a gage glass, or other acceptable device. Where the allowance pressure exceeds 1724 kPa (250 psi), the gage glasses shall be of the flat type instead of the common tubular type.
(2) Gage glasses shall be in continuous operation while the boiler is steaming.
(3) Double-ended firetube boilers shall be equipped as specified in this paragraph and paragraph (e) of this section except that the required water level indicators shall be installed on each end of the boiler.
(4) Externally fired flue boilers, such as are used on central western river vessels, shall be equipped as specified in paragraphs (b) (1) through (3) of this section except that float gages may be substituted for gage glasses.
(c) Water columns. (Modifies PG60.2.) The use of water columns is generally limited to firetube boilers. Water column installations shall be close hauled to minimize the effect of ship motion on water level indication. When water columns are provided they shall be fitted directly to the heads or shells of boilers or drums by 1 inch minimum size pipes with shutoff valves attached directly to the boiler or drums, or if necessary, connected thereto by a distance piece both at the top and bottom of the water columns. Shutoff valves used in the pipe connections between the boiler and water column or between the boiler and the shutoff valves required by PG60.6 of the ASME Code for gage glasses, shall be locked or sealed open. Water column piping shall not be fitted inside the uptake, the smoke box, or the casing. Water columns shall be fitted with suitable drains. Cast iron fittings are not permitted.
(d) Gage glass connections. (Modifies PG60.3.) Gage glasses and gage cocks shall be connected directly to the head or shell of a boiler as indicated in paragraph (b)(1) of this section. When water columns are authorized, connections to the columns may be made provided a close hauled arrangement is utilized so that the effect of ship roll on the water level indication is minimized.
(e) Gage cocks. (Modifies PG60.4.) (1) When the steam pressure does not exceed 250 pounds per square inch, three test cocks attached directly to the head or shell of a boiler may serve as the secondary water level indicator.
(2) See paragraph (d) of this section for restrictions on cock connections.
(f) Pressure gages. (Modifies PG60.6.) Each double-ended boiler shall be fitted with two steam gages, one on either end on the boiler.
(g) Salinometer cocks. In vessels operating in salt water, each boiler shall be equipped with a salinometer cock or valve which shall be fitted directly to the boiler in a convenient position. They shall not be attached to the water gage or water column.
(h) High-water-level alarm. Each watertube boiler for propulsion must have an audible and a visible high-water-level alarm. The alarm indicators must be located where the boiler is controlled.
[CG FR 6882, 33 FR 18815, Dec. 18, 1968, as amended by CGD 8179, 50 FR 9433, Mar. 8, 1985; CGD 83043, 60 FR 24772, May 10, 1995]
ver las páginas en versión mobile | web
ver las páginas en versión mobile | web
© Copyright 2013, vLex. All Rights Reserved.
Contents in vLex United States
Explore vLex
For Professionals
For Partners
Company
Other documents:
bcs has texas brown befuddled -- sooners land spot in big 12 championship | Eatery Owner a Smoker's Hero | sienkowski, sigmund m. | Venus Good As New in Return | Sentencia nº 5713 de Consiglio di Stato, October 28, 2008 | Sentencia nº 5660 de Consiglio di Stato, November 12, 2009 | decisión de tribunal primero de primera instancia en funciones de control de tachira extensión san cristóbal de june 05 2007 | decisión de tribunal primero de primera instancia en funciones de control de anzoategui (extensión barcelona), de november 02, 2005